Viessmann Boiler: Cascade heat generator scan and output entry
Cascade heat generator scan and output entry on a Viessmann boiler: After a restart or new configuration, the controller scans the bus for about one minute. Output values cannot be entered during this scan. A generator that reports its output is entered automatically. A generator that reports no output is entered as 15 kW and can be changed by hand. Identical boilers only need one release each.
Applies to: Versatronik 200 cascade, output boiler stage list
How to fix cascade heat generator scan and output entry: step by step
- Wait for the SCAN display to finish (about 1 minute).
- Select the boiler and stage with the Prog button.
- Enter or adjust the HS output value; use --- for not available and 0 for available but deactivated.
- Check the entered output matches the actual boiler.
If the unit shows an error code, look it up: Viessmann Boiler codes
More commissioning tips for boiler
Source: Versatronik 200 installation and operating manual, p. 109. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.