Viessmann Boiler: Bus communication problems
Bus communication problems on a Viessmann boiler: Controller and bus devices do not communicate correctly.
Applies to: Versatronik 200 BUS network
Common causes of bus communication problems
- Bus or sensor lines run too close to mains cables.
- Bus supply voltage is too low.
- Poles or switches are wrong.
How to fix bus communication problems: step by step
- Check the bus lines and sensor lines run separately, away from mains cables.
- Check the bus feed: at least 8 V DC must be measured between the + and - terminals of the BUS connector (connectors 18 and 19).
- If the bus voltage is lower than 8 V DC, install an external power supply.
- Check the communication symbol in the display or in Service / Communic MM 1.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Versatronik 200 installation and operating manual, p. 166. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.