Updated · by Aurora Star Tech Inc.

Burner heat demand wiring on a Viessmann boiler: Terminals 29 and 30 call for heat from stage 1. Terminals 32 and 33 call for stage 2 of a 2-stage boiler, or the second boiler in a lead-lag setup. Both are potential-free contacts, usually wired to the TT contacts on the boiler. Staging depends on control settings.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Versatronik 200 burner demand outputs

How to fix burner heat demand wiring: step by step

  1. Wire single-stage boilers with 2-conductor cable.
  2. Wire 2-stage boilers with 4-conductor cable.
  3. Confirm the terminal locations and requirements in the boiler manual or control manual.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Source: Versatronik 200 installation manual, p. 15. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.