Viessmann Boiler: Boilers not communicating or not staging
Boilers not communicating or not staging on a Viessmann boiler: Boiler communication depends on unique LON addresses. A boiler that does not appear to be communicating is started last.
Applies to: Versatronik 300 cascade boilers
Common causes of boilers not communicating or not staging
- Duplicate LON address, including address 77
- Boiler not reachable on the LON network
How to fix boilers not communicating or not staging: step by step
- Check that each boiler has a unique LON address, starting from 77.
- Check the B1 to B16 status screens for boilers that show no status or temperature.
- Check the Boiler config menu for the correct number of boilers.
- If all non-ECO lock boilers are running and set point is still not met, check the AUX output.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Versatronik 300 Cascade Control manual, p. 30 and p. 32. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.