Viessmann Boiler: AUX heat demand input wiring
AUX heat demand input wiring on a Viessmann boiler: The AUX input takes a potential-free dry contact. Closing the contact requests heat at a fixed set point. It can be used with outdoor reset or on its own as an enable/disable.
Applies to: AUX terminals, heat demand
How to fix aux heat demand input wiring: step by step
- Wire the BMS or mechanical control through a field-supplied relay to the AUX terminals.
- Use an AC or DC relay coil with the correct control voltage. The contact closure is the heat demand.
- Use low-voltage wiring and keep it away from 120/240 VAC conductors.
- Set the demand set point as described in the coding steps.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Source: Versatronik 300 Cascade Control technical, installation and configuration manual, p. 11. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.