Other: Boiler tips (part 4 of 50)
Short, practical technician tips on other for boiler. Check each one against the manual for your exact model before acting.
Remote controller LED indicator meaning
Navien · Remote controller
A flashing green LED means the burners are on. A flashing red LED means there is an error.
- If the red LED flashes, read the code on the display and check the error code guide.
- If the green LED flashes, the burners are firing.
RS-485 cable length and cable type
Navien · Modbus RTU RS-485 network
Maximum RS-485 distance is about 3,000 ft at 57600 baud. Higher baud rates reduce the usable distance. Use twisted pair cable such as UTP or CAT5 for signal quality.
- Keep the run within the distance for the chosen baud rate.
- Use twisted pair cable (UTP or CAT5).
Shutting the boiler down for a long period
Navien · NCB700 boilers not in use for a long time
Drain the boiler and cut power so it does not freeze or get damaged while unused.
- Completely drain the water out of the boiler.
- Disconnect the power supply to the boiler.
Termination resistor DIP switch
Navien · R1 and R2 ports
Enable termination only if the gateway is the last device on the serial trunk. Termination also overrides bias resistors if both are connected.
- If the gateway is the last device on the trunk, move the TERM DIP switch to the right on the port in use.
- Leave termination off for gateways in the middle of the trunk.
- Power cycle the gateway after changing the switch, since changes do not apply while powered.
Turn off gas to the boiler for service
Navien · NCB700
Procedure before performing service on the boiler. The boiler has no pilot and uses an ignition device.
- Turn off all electrical power to the boiler if service is to be done.
- Set the thermostat or control to the lowest setting.
- Close the main manual gas valve (main valve).
UL compliance conditions for gateway installation
Navien · Navien Modbus/BACnet gateway
Conditions the gateway must meet for UL compliance.
- Power the gateway from a listed LPS or Class 2 supply rated for the expected temperature range.
- Use interconnecting power connectors and cable that meet local electrical code, the expected temperature range, and the gateway current and voltage rating.
- Keep the interconnecting power cable 3.05 m (118.3 in) or shorter, made of VW-1, FT-1 or better rated material.
- If the ambient is above 65 °C, install in a restricted access area that needs a key or special tool.
- Do not connect this device to a LAN segment that has outdoor wiring.
Use only inhibited propylene glycol in space heating
Navien · Space heating loop antifreeze
Only inhibited propylene glycol made for space heating systems may be used as antifreeze. Ethylene glycol is toxic and attacks gaskets and seals.
- Confirm the antifreeze is inhibited propylene glycol made for space heating before adding it.
- Do not add ethylene glycol.
Use only with Navien combi-boilers
Navien · NCB-H and NFC Series primary manifold
The manifold is approved only for Navien NCB-H and NFC Series combi-boilers and must not be used with other manufacturers' products. Installation and service must be done by a qualified installer or service agency.
Vent installation detector limits
Navien · NCB700 vent installation detector
The vent installation detector only checks that the pipe is inserted to 70 mm in the exhaust collar. It does not detect leaks, pipe separation past the collar, blocked vents, vent movement, or a worn or stuck switch. Do not rely on it as a carbon monoxide alarm or safety switch. Inspect all vent joints regularly.
- Inspect all vent joints at regular intervals.
- Do not rely on the detector to find leaks, separated joints or blockages.
- Use a carbon monoxide detector as a separate safeguard.
View error history
Navien · Front panel display
The display keeps the 10 most recent errors. The newest error is at the top of the list.
- Press the Menu button.
- Select 4. Error History.
- Turn the Command dial to scroll the list.
- Press the Back button to return to the previous screen.
Wire labelling and verification during control work
Navien · NCB700 boilers
Wiring errors can cause improper and dangerous operation. Label every wire before disconnecting it when working on the controls, and verify proper operation after any service.
- Label all wires before disconnecting them.
- Verify proper operation after servicing.
Wiring a low water cutoff (LWCO) switch
Navien · NCB700 low water cutoff wiring
The boiler supplies 24 VAC to the LWCO power terminals (CNC3). For line-voltage LWCO switches, the manual shows a typical method where the burner and control circuits share the same voltage, using a jumper between the switch terminals.
- Connect the LWCO switch power to the 24 VAC terminals (CNC3) on the boiler board.
- For a line-voltage switch, use the typical wiring with a jumper as shown in the manual.
- Confirm the wiring matches the diagram before power-up.
3-way valve motor must be disconnected for heating-only use on TRX150 / TRX199
NTI · TRX150 and TRX199 models, heating-only installs
If the boiler only serves heating and is not connected to an indirect water heater, the 3-way valve motor must be disconnected while the boiler runs in central heating mode. This locks the valve in CH so freeze protection works. Leaving the valve connected can disable freeze protection and cause property damage.
- Confirm the boiler is heating only, with no indirect water heater.
- Disconnect electrical power before working on the wiring.
- Disconnect the 3-way valve motor so it stays locked in central heating mode.
Antifreeze selection
NTI · TRX150
Only use antifreeze made for hydronic systems that contains propylene glycol. Never use automotive or standard ethylene glycol antifreeze, which attacks seals and is toxic. Check the antifreeze is compatible with the stainless steel heat exchanger.
- Use propylene glycol antifreeze made for hydronic systems.
- Use the mix and quantities the antifreeze maker gives for your region.
- Do not use automotive or ethylene glycol antifreeze.
Auto Boost behaviour
NTI · NTI TRX boilers, outdoor reset
Auto Boost (4.7.5 = 1) raises the outdoor reset slope by 10 percent every 10 minutes while a call for heat stays on, up to 2 times the nominal slope (4.2.2). When the call is satisfied, the slope drops 1 percent per minute back to the nominal value. Only works when 4.2.1 = 3 or 4.
Canada vent installation requirements
NTI · Canadian installations
Extra requirements for Canadian installations.
- Use a vent system certified to ULC-S636.
- Keep the first 3 ft of vent pipe from the flue outlet readily accessible for inspection.
- Do not mix components with other vent systems or unlisted pipe or fittings.
- Keep plastic vent and boiler parts at least 8 in from high heat sources (100 F / 37 C or greater).
Carbon monoxide detector placement
NTI · All installations
Required CO detector placement in the home.
- On each floor with bedrooms, place a CO detector and alarm in the living area outside the bedrooms.
- Also place one in the room that houses the boiler.
- Use detectors that comply with NFPA 720 (latest edition).
Ceramic fiber dust in the combustion chamber
NTI · TRX150
Combustion chamber insulation contains ceramic fiber that can form cristobalite at high temperature. Limit dust exposure.
- Wet the combustion chamber lining before disturbing it to prevent dust.
- Wear an N95 NIOSH certified respirator, long sleeves, gloves and eye protection.
- Wash contaminated clothing separately and rinse the washer.
- If dust reaches the eyes, irrigate immediately. If breathing is affected, move to fresh air.
Condensate float switch
NTI · TRX boilers
The condensate collection system has a float switch that monitors condensate level and prevents backup into the boiler.
Control panel buttons and display layout
NTI · TRX150 control panel
Front panel has ON/OFF, DHW +/- (item 2), MENU (item 3), HISTORY (item 4), RESET (item 5), OK (item 6), ESC (item 7), CH +/- (item 8) and the display (item 9). The ON/OFF button lights white when the boiler has power and stays dark during an error or power failure. The RESET button lights red on a lockout. A short MENU press opens the user menu and a long MENU press opens the info menu.
- Press ON/OFF to power the boiler on or off.
- Press MENU briefly for the user menu.
- Press and hold MENU for the info menu.
- Use the CH +/- or DHW +/- buttons to change setpoints from the home screen.
Day and night room setpoints
NTI · NTI TRX boilers with room sensor
Daily comfort setpoint factory 70 F, night reduced setpoint factory 61 F. Only applies with NTI room sensor. Zones 1 and 2 can have different setpoints, applied with the selected mode and time program. Allowed target ranges depend on each other as shown in the setpoint graph.
Display icons and what they mean
NTI · TRX150 control panel
The display shows boiler status, temperature in °F with a bar level, error codes with the word ERROR, a RESET request on lockout, and menu settings. Icons show: technical assistance request, flame with power level, CH heating set or active, DHW set or active, hot water comfort (combi only), antifreeze active (boiler off or on), AUTO outdoor reset control, error signal, outdoor sensor connected (optional) and WiFi active.
- If the error icon is lit, read the code and description on the display.
- If the RESET request appears, press RESET after the cause is fixed.
- If the technical assistance icon shows, call for service.
Do not add cold make-up water to a hot boiler
NTI · TRX boilers, system fill and service
Adding cold water to a hot boiler causes thermal shock that can crack the heat exchanger. This damage is not covered by warranty. Also, continual fresh make-up water shortens boiler life and must be stopped by repairing leaks at once.
- Let the boiler cool before adding make-up water.
- Repair leaks in the boiler or piping right away.
Do not adjust excess flow valve screws without analyzer
NTI · NTI TRX150 gas valve
Screws 2 (offset) and 4 (throttle) on the gas valve must not be removed or adjusted without a calibrated combustion analyzer. Doing so can cause fire, property damage or serious injury.
- Leave the EFV offset and throttle screws alone unless a calibrated combustion analyzer is connected.
Do not use solvents or operate with missing parts
NTI · TRX150
Solvents can damage boiler components. Missing condensate trap parts make the boiler unsafe to run.
- Clean boiler components with water or approved solution only.
- If any condensate trap part is missing, do not run the boiler. Replace the whole trap assembly.
Exhaust vent slope, support and terminations
NTI · Exhaust vent and intake installation
Support the vent so it does not carry its own weight on the boiler connections, and keep it draining back to the boiler.
- Pitch the exhaust vent at least 1/4 inch per foot back toward the boiler so condensate drains.
- Do not use vent connections to support the piping.
- Insert the supplied exhaust and intake screens into both terminations to stop debris and birds getting in.
- Pipe exhaust and intake separately. Do not share a common exhaust or intake with other appliances.
Freeze protection is off when the boiler has no power
NTI · TRX boilers
The control's freeze protection does not work if power is lost. Plan piping and location with freeze risk in mind. Freeze damage is not covered by warranty.
Glycol limits for DHW and IWH loops
NTI · TRX boilers with glycol
Use only food grade propylene glycol rated GRAS for indirect water heater loops. Glycol content must not exceed 50% unless the manufacturer says otherwise. Non-GRAS glycol is only allowed in closed loop CH applications. Check glycol periodically so it does not turn acidic. Never use automotive or standard ethylene glycol.
- Use food grade propylene glycol (GRAS) for IWH loops.
- Keep glycol at or below 50% of the liquid.
- Test glycol periodically for acidity.
Massachusetts venting requirements
NTI · Massachusetts and local code installations
Signage and piping labels required in Massachusetts and where state or local codes require them.
- Do not take combustion or dilution air from a bedroom or bathroom.
- Where a through-the-wall vent is less than 7 ft above grade, mount a metal or plastic sign at least 8 ft above grade in line with the vent.
- Sign text must read 'GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS' with letters at least 0.5 in high.
- Label exposed piping every 10 ft and concealed piping every 3 ft, at all direction changes, and on both sides of any wall or ceiling penetration.
- Labels must be black lettering at least the pipe diameter in height, up to 2 in maximum.
Overheat cutoff and lockout at 212°F
NTI · TRX boilers
The temperature controls are UL 353 listed. They shut off the fuel when the set point is reached. At 212°F, the boiler goes into safety shutdown and lockout and needs a manual reset.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.