Navien Tankless Water Heater: NHW700 freeze protection not working
NHW700 freeze protection not working on a Navien tankless water heater: Freeze protection runs the pump and fires the burner based on the outlet sensor.
Applies to: NHW700-120SE/160SE/180SE/199SE, NHW700-160SU/180SU/199SU, NHW700-160AI/180AI/199AI, NHW700-160AE/180AE/199AE
Common causes of nhw700 freeze protection not working
- Outlet and inlet sensors both failed
- No power to the heater
How to fix nhw700 freeze protection not working: step by step
- It turns on when the water stays below the set point for 20 seconds and off when it is 4 C above it for 20 seconds.
- Set point: 1 C on universal/indoor models, 0 C on exterior models.
- If the outlet sensor fails it uses the inlet sensor. If both fail there is no freeze protection: fix any E407/E421/E441 first.
- It needs power and does not run during normal firing.
If the unit shows an error code, look it up: Navien Tankless Water Heater codes
Models
NHW700-120SENHW700-160AENHW700-160AINHW700-160SENHW700-160SUNHW700-180AENHW700-180AINHW700-180SENHW700-180SUNHW700-199AENHW700-199AINHW700-199SENHW700-199SU
Source: Navien NHW700 Non-Condensing Water Heater Service Manual (V1.0, Apr 2023), 6.4 p.87. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.