Navien Tankless Water Heater: E110 air pressure fault on NHW700

Updated · by Aurora Star Tech Inc.

E110 air pressure fault on NHW700 on a Navien tankless water heater: The fan is spinning faster than normal but the APS reads less pressure than it should. Usually a blocked air or exhaust path.

Homeowner with a tankless water heater problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: NHW700-120SE/160SE/180SE/199SE, NHW700-160SU/180SU/199SU, NHW700-160AI/180AI/199AI, NHW700-160AE/180AE/199AE

Common causes of e110 air pressure fault on nhw700

  • Blocked or crushed vent or air intake
  • Rain water collected in a vertical intake pipe
  • Exhaust being drawn back into the intake
  • Debris or soot on the heat exchanger
  • Condensate in the exhaust duct or APS hose
  • Broken or blocked APS hose, bad APS
  • Old PCB software

How to fix e110 air pressure fault on nhw700: step by step

  1. Gas unit: only a qualified gas technician should work on it. Power off at the switch before unplugging any connector.
  2. Check the exhaust and intake outside for blockage, damage or nests. Clear them and reset.
  3. Check for water in the intake pipe, condensate in the exhaust duct and inside the APS and its hoses.
  4. Check the exhaust is not being pulled back into the intake.
  5. If it comes and goes, run the heater at fixed min and max (DIP 1-1 and 1-2) and compare fan speed to normal. Higher than normal points to a blockage or APS hose problem.
  6. Check the APS hose and the APS voltages.
  7. Check the heat exchanger for debris or soot.
  8. Manual says to fit the latest PCB version if it keeps happening. Put DIP 1-1/1-2 back to OFF when done.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Navien Tankless Water Heater codes

Models

NHW700-120SENHW700-160AENHW700-160AINHW700-160SENHW700-160SUNHW700-180AENHW700-180AINHW700-180SENHW700-180SUNHW700-199AENHW700-199AINHW700-199SENHW700-199SU

Source: Navien NHW700 Non-Condensing Water Heater Service Manual (V1.0, Apr 2023), 7.3.8 p.104, 5.11 p.81, 5.12.1 p.82. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.