Lifebreath Hrv: Water in the bottom of the HRV
Water in the bottom of the HRV on a Lifebreath hrv: Standing water inside the cabinet.
Applies to: Lifebreath RNC series HRV
Common causes of water in the bottom of the hrv
- Drain pans plugged
- Drain lines connected wrong
- HRV not level
- Drain lines blocked or kinked
- Core not installed right
How to fix water in the bottom of the hrv: step by step
- Kill power at the HRV disconnect before opening the unit. Some units have more than one power feed.
- Check the drain line, spout and P-trap for blockage, mould or kinks.
- Flush the line with warm soapy water. Replace it if it is worn, bent or won't come clean.
- Check the unit is level.
- Pull the core and reinstall it: bottom edge on the bottom support first, line it up with the other 3 supports, push on the sides, not the middle.
If the unit shows an error code, look it up: Lifebreath Hrv codes
Models
Source: Lifebreath RNC5-ES Homeowner's Guide (69-RNC5-OWNERS 012616), Troubleshooting, p. 14; Maintenance Routine, p. 12-13. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.