Lifebreath Hrv: Poor airflow from HRV
Poor airflow from HRV on a Lifebreath hrv: Weak supply or exhaust air at the grilles. Usually something plugged or closed.
Applies to: Lifebreath RNC series HRV
Common causes of poor airflow from hrv
- 1/4 in (6 mm) bird screen on an outside hood plugged
- Dirty filters
- Core blocked
- Grilles closed or blocked by furniture
- Balancing dampers closed
- Low supply voltage
- Duct run too restrictive
- Speed set too low on the control
- Unit not balanced
How to fix poor airflow from hrv: step by step
- Kill power at the HRV disconnect before opening the unit. Some units have more than one power feed.
- Check both outside hoods first. Clear leaves, snow or frost off the mesh.
- Pull and wash the filters, then pull and wash the core.
- Walk the house and open any closed or blocked grilles.
- Check the balancing dampers are open and set.
- Turn the speed up on the wall control and see if flow comes back.
- Check the duct install for crushed or long flex runs.
- If still weak, have an electrician check supply voltage and rebalance the HRV airflows.
If the unit shows an error code, look it up: Lifebreath Hrv codes
Models
Source: Lifebreath RNC5-ES Homeowner's Guide (69-RNC5-OWNERS 012616), Troubleshooting, p. 14. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.