Viessmann Boiler: Outdoor temperature sensor installation and wiring
Outdoor temperature sensor installation and wiring on a Viessmann boiler: Mount the sensor where it will read outdoor air properly. Use shielded twisted pair if the cable runs near 120/240 VAC wiring, and ground only one end of the shield.
Applies to: Outdoor sensor on Versatronik COMO OT
How to fix outdoor temperature sensor installation and wiring: step by step
- Mount the sensor on the outside of the building, 2 to 2.5 m above ground, on the north or north-west wall.
- In multi-storey buildings, mount it in the upper half of the second storey.
- Keep the sensor away from windows, doors, air vents, balconies and gutters.
- Do not paint over the sensor housing.
- Wire the field cable to the terminals inside the sensor and run it through the strain relief at the bottom of the housing.
- Refit the sensor cover.
- Run the cable to the controller sub-base and connect it to terminals 5 and 6.
- Keep the cable away from high voltage conductors. If that is not possible, use stranded twisted shielded wire and ground only one end of the shield.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Versatronik COMO OT manual, p. 9. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.