Viessmann Boiler: Mounting the wall base and fitting the room controller
Mounting the wall base and fitting the room controller on a Viessmann boiler: Mount the base at about eye level and wire it to the boiler OT-BUS. Terminals 1+2 are the bus and can be swapped because the connector is polarity-protected. Terminals 3+4 are for the remote telephone switch and 5+6 for the outdoor sensor, both optional. Terminal 1 is on the left.
Applies to: Versatronik COMO OT wall base and cover
How to fix mounting the wall base and fitting the room controller: step by step
- Fix the base to the wall at about eye level.
- Connect terminals 1+2 on the base to the OT-BUS terminals on the boiler. The polarity can be swapped.
- Connect the remote telephone switch to terminals 3+4 if one is used.
- Connect the outdoor sensor to terminals 5+6 if one is used.
- Snap the top part on: hook it in at the centre of the top edge, pivot it down onto the base and press it on.
- To remove, lever the cover off from the underside with a screwdriver, then pivot the top upwards.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Versatronik COMO OT manual, p. 8. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.