Viessmann Boiler: Connect gateway to Vitotronic control over LON and BACnet/IP
Connect gateway to Vitotronic control over LON and BACnet/IP on a Viessmann boiler: Wire the gateway to the boiler control and the building network. Use the connection diagram that matches the control and supply voltage.
Applies to: Vitotronic 300 GW5B, GW6B (single and cascade), Vitotronic 300-K MW2C (Vitodens 200, B2HA)
How to fix connect gateway to vitotronic control over lon and bacnet/ip: step by step
- Make sure the LON communication card is installed in the control. Refer to the boiler or system control manual.
- Plug the supplied 3 ft (91 cm) CAT-5 cable into the RJ45 socket on the control and the other end into the RJ45 socket inside the Versatronik 585 gateway.
- Plug the BACnet/IP RJ45 communication cable from the building management system into the gateway.
- For 120 VAC gateways, connect the plug-in power cord.
- For 24 VAC gateways, connect a field-supplied 24 VAC power supply to the gateway.
- On the Vitotronic 300-K MW2C, the communication card is required for Vitocontrol-S and the MW2C for Vitodens B2HA boilers.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Source: Versatronik 585 and 585D BACnet IP gateway manual, p. 8. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.