Short, practical technician tips on settings shortcuts for combi boiler. Check each one against the manual for your exact model before acting.

Show fan frequency on the display (parameter 22)

FlowMax · FLOWMAX-120 condensing combi

Setting parameter 22 to 01 makes the display show the fan frequency for 10 minutes while the unit runs.

  1. Enter the parameter menu (PL 0).
  2. Select parameter 22 and set it to 01 (00 = off).
  3. Confirm with S, then switch the unit off and on.
  4. While the unit runs, the display shows the fan frequency for 10 minutes.

Change gas type with DIP switch 2

Navien · NCB-250/150H, NCB-240/130H, NCB-240/110H, NCB-190/080H, NCB-190/060H

DIP switch 2 #1 sets natural gas or propane and must match the rating plate and the Start-up Wizard.

  1. Turn power off before removing the front cover.
  2. DIP switch 2, #1: OFF = natural gas, ON = propane.
  3. A gas type that does not match the rating plate can show E773/E788.

Set the altitude with DIP switch 2

Navien · NCB-250/150H, NCB-240/130H, NCB-240/110H, NCB-190/080H, NCB-190/060H

DIP switch 2 #2 and #3 select the altitude band.

  1. 0-1,999 ft: 2 OFF, 3 OFF.
  2. 2,000-5,399 ft: 2 ON, 3 OFF.
  3. 5,400-7,699 ft: 2 OFF, 3 ON.
  4. 7,700-10,100 ft: 2 ON, 3 ON.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.