NTI Boiler: Clean the heat exchanger and combustion chamber
Clean the heat exchanger and combustion chamber on a NTI boiler: Cleaning requires a nylon brush and an FDA-approved liquid lime scale remover. Insulation contains ceramic fiber. Wear a NIOSH-certified N95 respirator, gloves and eye protection, and dampen the lining to limit dust.
Applies to: TRX150
Common causes of clean the heat exchanger and combustion chamber
- Scale or dirt in the combustion chamber
How to fix clean the heat exchanger and combustion chamber: step by step
- Make sure power and gas are off, and let the boiler cool before draining water.
- Remove the silencer.
- Disconnect the gas pipe by unscrewing its two nuts. Remove the gas pipe.
- Remove the gas diaphragm if one is fitted.
- Disconnect the electrical connections to the electrodes, igniter and blower.
- Unscrew the four nuts on the burner door and remove the door.
- Check the back wall insulation and replace it if needed.
- Disconnect the condensate hose and siphon cap from the boiler.
- Clean the heat exchanger with the nylon brush and lime scale remover, then rinse.
If the unit shows an error code, look it up: NTI Boiler codes
Models
TRX085TRX110CTRX150TRX199TRX199C
Source: NTI TRX150 manual, p. 90. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.