NTI Boiler: Running a pump by hand
Running a pump by hand on a NTI boiler: Quick way to find out whether the control or the pump is at fault.
Applies to: Trinity Tft60, Tft85, Tft110, Tft154, Tft201, Tft285, Tft340, Tft399
How to fix running a pump by hand: step by step
- Open the pump diagnostic page on the display
- Switch the pump on manually
- Measure for 120 VAC at the pump terminals on the line voltage strip
If the unit shows an error code, look it up: NTI Boiler codes
Models
Tft60Tft60Tft85Tft85Tft110Tft110Tft154Tft155Tft175Tft200Tft201Tft250Tft285Tft300Tft340Tft399Tft399
Source: NTI Trinity Tft399 Installation and Operation Manual (2018-09-07), Sec. 16.0 Troubleshooting. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.