General: Water not heating / high head when in reclaim
Water not heating / high head when in reclaim on a general: Heat reclaim not heating water, or head pressure climbing when reclaim kicks in.
Common causes of water not heating / high head when in reclaim
- Three-way solenoid not diverting, so the hot gas never goes to the reclaim condenser, because of a coil or valve fault
- Reclaim condenser fouled on the water or refrigerant side, which cuts heat transfer
- Parallel reclaim condenser too small for full load, so head rises
- Check valve leaking, letting gas or liquid bypass
- Refrigerant stranded in the idle condenser, which starves the active circuit
How to fix water not heating / high head when in reclaim: step by step
- Verify the three-way valve position and coil voltage when reclaim is called
- Compare reclaim condenser capacity to the design load
- Check the check valve for leak-by, a hot line where it should be cold gives it away
- Check ORI and ORD operation, the outlet regulating valves, since stuck ones trap charge
- Measure water in and out temperatures to see whether the reclaim coil is picking up heat
- Have a licensed refrigeration tech do any refrigerant recovery or valve replacement
If the unit shows an error code, look it up: Navien General codes Trane General codes
Source: General HVAC service practice — verify per model. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.