General: Runs but not pumping
Runs but not pumping on a general: Vacuum pump runs but won't pull down. Two causes: worn pump or leaking discharge valves. Two quick tests tell you which. Do them before you blame the system, because a weak pump makes a tight system look leaky.
Common causes of runs but not pumping
- Worn pump, low power draw and weak pulldown
- Leaking discharge valves, so vacuum bleeds back
- Oil contaminated or low, so the pump cannot pull deep
- Leaking gauge or hose connection making it look like a pump problem
How to fix runs but not pumping: step by step
- Read watts or VA. Below the rating means worn.
- Pinch off the suction and watch the gauge. It should pull 25 to 28 in. Hg in seconds.
- If vacuum decays, for example 20 down to 10 in. Hg, the valves are leaking.
- Check the oil level and condition, and change it if it is dirty.
- Test with the pump isolated from hoses to rule out leaks.
- Replace the leaking valves or the pump.
If the unit shows an error code, look it up: Navien General codes Trane General codes
Source: General HVAC service practice — verify per model. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.