General: No heat — low-voltage stat diagnostic (16 steps)

Updated · by Aurora Star Tech Inc.

No heat — low-voltage stat diagnostic (16 steps) on a general: This is a 16-step way to find out whether a no-heat call is the furnace or the thermostat and its wiring. The idea is to take the stat out of the picture at the furnace first, then work back toward the wall one measurement at a time. Do it carefully. Keep power off whenever you move a jumper, put the furnace panel back on so the door switch is properly closed, and leave anything gas related to a licensed tech.

Homeowner with a heating or cooling system problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Common causes of no heat — low-voltage stat diagnostic (16 steps)

  • Thermostat or subbase failed, including dead batteries on an electronic stat
  • Broken or loose thermostat wire, R or W
  • Whole thermostat cable damaged
  • Furnace control or board problem, if heat will not start at the board either
  • Mercury stat that no longer makes contact

How to fix no heat — low-voltage stat diagnostic (16 steps): step by step

  1. Turn power off, then put a jumper across R and W at the furnace board.
  2. Power on with the door switch closed, and give the furnace its normal start time. If the furnace starts, the problem is the stat or the wiring. If it does not, the problem is the furnace. Remove the jumper.
  3. At the stat subbase read R to W. You should see 25 to 27 Vac.
  4. No voltage means a wire fault, so read R to G and R to Y. If you get none, read at the source, and the R wire is bad. If you do get them, the W wire is bad.
  5. Swap to a spare conductor for the bad wire.
  6. Still nothing anywhere means the whole cable is broken and must be replaced.
  7. Voltage present, so jumper R to W at the subbase. If heat starts within the normal time, the stat is bad. Check batteries first on electronic stats.
  8. Replace mercury stats with a subbase. Remove all jumpers and confirm normal operation.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Navien General codes Trane General codes

Source: General HVAC service practice — verify per model. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.