General: Draft complaints
Draft complaints on a general: Draft complaints are almost always an air-velocity or distribution issue, not a sign the equipment is broken. Before changing anything, find where the air is coming from and how fast it is moving at the register, since people feel anything much over about 500 fpm as a draft.
Common causes of draft complaints
- Register velocity over 500 fpm at the occupied zone
- Unbalanced system sending too much air one place and too little elsewhere
- Too much air delivered to one room
How to fix draft complaints: step by step
- Check the airflow with a smoke pencil to see where it travels, and measure it with an anemometer. Confirm the number before you decide anything
- Redirect the louvers away from where people sit
- Swap in a broader-diffusing register to slow and spread the air
- Partly close the branch damper for that room
- Rebalance the whole system once the high spots are corrected, and recheck the comfort afterward
If the unit shows an error code, look it up: Navien General codes Trane General codes
Source: General HVAC service practice — verify per model. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.