Electrical: No power / low voltage
No power / low voltage on a electrical: No power or low voltage at the load. Meter first, guess later. Work back from the load toward the source until you find where the voltage drops.
Common causes of no power / low voltage
- Open sequencer
- Open thermostat or open control circuit
- Low line voltage at the supply
- Low transformer output
How to fix no power / low voltage: step by step
- Meter the line voltage at the panel and at the unit
- Meter the transformer secondary; compare to the rated 24 volts
- Check the thermostat for an open and the wiring for loose connections
- Check the sequencer for a closed contact on a heat call
- Look for loose or burned terminals and fix with power off
- Have the utility or an electrician look at it if the supply itself is low
Source: General HVAC service practice — verify per model. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.