Navien Tankless Water Heater: Run test mode (fan, flow valve, venturi, pump, mixing valve)
Run test mode (fan, flow valve, venturi, pump, mixing valve) on a Navien tankless water heater: Test mode drives individual parts so you can check them one at a time.
Applies to: Navien NPE-A2 (built-in recirculation) and NPE-S2 condensing tankless water heaters: NPE-150S2, NPE-180A2/S2, NPE-210A2/S2, NPE-240A2/S2
How to fix run test mode (fan, flow valve, venturi, pump, mixing valve): step by step
- Hold Menu and Back together for 3 seconds and choose 3. Test Mode.
- Fan Motor: fan ramps from 0 to max and back, repeating.
- Water Flow Adjust Valve: full open to full close over about 12 s, shows 0-100%.
- Dual Venturi: on when entered, Up/Down toggles on/off.
- Pump (A2) / Ext. Pump (S2): runs 10 s, stops 5 s, 5 times (75 s).
- Mixing Valve (S2 only): full open to full close over about 10 s, shows 0-56%.
If the unit shows an error code, look it up: Navien Tankless Water Heater codes
Models
NPE-150S2NPE-180A2NPE-180S2NPE-210A2NPE-210S2NPE-240A2NPE-240S2
Source: Navien NPE-A2/S2 Installation Manual, 7.4.2 p.95-96; 7.5 p.98-99, p.105-107. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.