Updated · by Aurora Star Tech Inc.

Bypass the 3-minute timer and clear a lockout with TEST (PRL-JEC) on a Rheem heat pump: Pressing TEST resets any active-protection lockout and the 3-minute anti-short-cycle timer, and energizes the unit even without a call. Use an insulated probe.

Homeowner with a heat pump problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Rheem/Ruud PRL-JEC heat pumps with Comfort Control2 ICC

How to fix bypass the 3-minute timer and clear a lockout with test (prl-jec): step by step

  1. Use an insulated probe to press TEST for one second, then let go
  2. With a call present the compressor and outdoor fan start and the display settles on c, C, h or H
  3. With no call a steady t shows and the compressor runs about 5 seconds
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Rheem Heat Pump codes

Models

RPRL-024JECRPRL-036JECRPRL-048JECRPRL-060JEC

Source: Rheem PRL-JEC Installation Instructions, Comfort Control2 section 12.5, p.23. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.