Updated · by Aurora Star Tech Inc.

Force cooling for charging with the FORCE button on a Bosch heat pump: A short press of FORCE (SW1) while the unit runs in cooling puts it in forced full-capacity operation for checking charge. On IDS 2.0 the display then shows a bar symbol followed by the compressor frequency.

Homeowner with a heat pump problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: BOVA IDS 2.0, IDS Premium Connected and IDS Light heat pumps

How to fix force cooling for charging with the force button: step by step

  1. Start the system in cooling mode
  2. Short press the FORCE button on the outdoor board
  3. Allow about 10 minutes to ramp up and 20 minutes to stabilise before taking charging readings
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Bosch Heat Pump codes

Models

Bosch IDS 2.0

BOVA-36HDN1-M20GBOVA-60HDN1-M20G

Bosch IDS Light

BOVA15-24BOVA15-36BOVA15-60

Bosch IDS Premium Connected

BOVA36-20BOVA60-20

Source: Bosch IDS Premium Connected BTC 762003301 D (02.2025), 17.2 Subcooling Charging p.43-44; IDS 2.0 service Rev3 (07.2021), 10.2.2 Force Mode Operation p.32. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.